Performed a cooling maintenance on a 2.5 ton, R-22 packaged air conditioner. Replaced filter and wash down condenser coil. Replaced dual run capacitor due to measuring below manufacturer specifications. Paid via check for repair. Running amps for compressor motor measured above data plate rating. Advise client system can fail at any day due to age and high compressor amps. System is currently cooling at the time of maintenance.