Found 2019 Goodman condenser with a failed/weak dual run capacitor. Replaced 80/5uF capacitor and tested system. Turned Honeywell T6 to cool (indoor temp 89°). All loads operational now. Checked refrigerant charge/ temp split. (23°). Found compressor pulling over its max rated start amps (LRA) on startup. Compressor pulling 151.8 amps and rated for 134 amps. Went over options with homeowner. Recommended Hyde’s Comfort Club maintenance plan for 15% savings off today’s call (and all calls for a year), 2x maintenance tune ups, and double the 1-year warranty to 2. Homeowner went with minimum option for just today’s repair. System is up and cooling properly now. Set thermostat to 88° as homeowner wanted to know best temp for unoccupied home. Put key back under rock on right side of courtyard right inside gate. Got email in file. 1-Year Warranty on capacitor.