02/24/2026- I arrived on site and replaced the faulty filter drier with warranty parts. I then preformed a nitrogen pressure test and leak search and verified that the unit is holding pressure without any leaks. I then pulled the unit into a vacuum below 500 microns before charging the unit up with 410a refrigerant. I have verified that the unit is cooling and heating properly at the time of service. I informed the customer that the unit is back in operation and to contact us if he has any questions, concerns, or issues for if we ever have to come back when it’s warmer to adjust the refrigerant charge. This unit is currently working properly and without issue.