Performed a cooling maintenance on a 2001 York 4 ton package unit. Filter is a 14 x 30 located in ceiling. Cycled cooling equipment, checked temp split and found it within range. Supply temperature is 54°. Verified voltages and system amperages. Capacitor for condenser fan motor is out of range 6.8/7.5uf. Informed client and recommended replacement to prevent a potential breakdown. Estimate is attached to email. Also washed condenser coil and cleared out condensation line. Cooling system is operational at this time.