Warranty call - customer is using too many appliances on (1) kitchen circuit, total power consumption is 3360W which is overloaded 20A circuit (2400W) - Solution: customer agreed with converting dishwasher circuit to dedicated line for single kitchen outlet that customer can use other appliances at the same time.