Diagnosis main breaker getting too hot and tripped Found: overloaded main breaker because total loads is approximately 320 amps while main service is capable of 200 amps. Recommend: relocate pool heater circuits ( two 50 amps circuits) by adding outdoor 100 amps sub-panel