Upon arrival to the scheduled system maintenance, I was shown to the a/h in the attic and c/u on the side of the home. I pulled off the panel door to inspect all electrical components connections, collect amp draw/voltage readings off electrical equipment, and check the unit for cleanliness. The a/h unit is clean. It has an older UV light system and the bulb needs to be replaced. UltraMax EZ UV Lamp Type GPH436T5L (17”) or GPH303T5L (12”). The customer said she would buy the replacement and have us install the new bulb. The office will need to follow up with an estimate to replace this bulb. The evaporator coil and blower fan are clean. The d/t temperature was 16° and within normal range. Photos uploaded to ST. All electrical components were secure and within factory range. I then vacuumed the condensate drain line to remove and blockage or debris. I ensured this was draining properly. The c/u system refrigerant charge is within normal range and all electrical components are secur