Completed inspection of equipment. Checked pressures, amp draw and capacitance. Visually inspected outside coil. Visually inspected interior coil and flushed drain line. Checked temperature differential and amp draw on inside unit. Also visually inspected attic space and ductwork. All duct is hung correctly and the insulation levels are within suggested height. After doing an inspection of the equipment today it is found that it is a little bit low on refrigerant and the capacitor is out of range. That’s a 2020 system which still has warranty for this new homeowner. Below is an estimate to have the work completed today as well as the maintenance option included. Customer excepted estimate. Added 1 pound of refrigerant and changed warranty capacitor. System is on cooling properly at this time with a 22° temperature differential.