Replace existing 3 phase 460V 2 HP 25 GPM well pump and wire.
Took voltage from the control box got 454 V amperage got 16.5 safe maxes 11 to 12. Told customer we will be back tomorrow with the pump and the new control box. We will try the control box 1st if it still doesn’t work then change the pump.
Replace two 119 gallon steel well tanks.
-Replace existing 62-gallon well tank -Replace all fittings associated with tank -Chlorinate well for sulfur smell