Completed one time tune up on your Lennox heat pump system. Drain was cleaned and filter was checked. All electrical components were tested to verify proper operating conditions. Found the run capacitor for the compressor to be low reading 63.2/9.3 rated for 70/10. The fan run side is within range but the compressor capacitor is just out of manufacture specifications. Estimate is attached to replace run capacitor. Thank you for your business. This job was captured in XOi Vision. Public Share Link - https://visionshare.xoi.io/?id=XA-A243-F5CD8B661A5844F3AA19226D3BC09DB2