Compressor change out complete. Recovered original refrigerant from system, removed existing compressor and filter dryer. Installed new compressor, new filter dryer, new crankcase heater and new compressor wiring harness. Pressure tested system and used soap bubbles on fittings to check for leaks, no leaks. Pulled vacuum below 500microns and added 5lbs of R22 to system, system is operating properly at this time. Condenser fan motor replacement complete. Removed existing condenser fan motor, unable to remove blades from motor due to the condition of motor shaft. Installed new condenser fan motor, new fan blades and new capacitor. Tested system, system is operating properly in cool at this time. Will need to return to replace rollout switch on heat strips.