Arrived today due to 2022 Rheem not cooling which is responsible for the entire house.There are two thermostats the upstairs was at 75° with a desired temperature of 70° and basement was at 72° with a desired temperature of 70° confirmed the indoor equipment was operational but outdoor equipment was non-operational.Attempted to access the mechanical room which was locked reached out to Eli which was unable to meet expressed this will cause lack of ability to diagnose indoor equipment.Blower motor was distributing air through the duct-work on each-floor.Began diagnostic on the outdoor equipment removed cover to the system finding contactor to be pulled in indicating thermostat was sending 24 volts to perform cooling function tested for power not receiving 240 volts.Disconnect was found to be in the off position flipped into the on position not regaining power to outdoor equipment indicating the breakers is tripped.Unfortunately was unable to gain access to the breaker due to being in th