Pumped down existing refrigerant to the condenser. Installed new TXV in the air handler evaporator coil. New insulation on the TXV bulb. Pressure tested system with nitrogen and pulled vacuum. Cleared condensation drain with CO2 and primed trap with water. Charged AC to 5 degrees subcooling per the unit’s chart. Tested operation of system. Everything is working at completion of service