Recovered existing refrigerant from the system. Installed new compressor. Removed existing liquid line filter dryer from the outside and installed a new one in the attic. Pressure tested system with nitrogen and pulled vacuum. Cleared primary drain with CO2 and primed trap with water. Sprayed JS685 insect deterrent in outdoor electrical panel. Weighed in factory charge of R-410A refrigerant. Charged AC to 10 degrees subcooling. Everything is working at completion of service.