During my diagnostic of the system, I discovered the following: the capacitor has failed, the contactor is pitted and charred, the condenser fan motor is leaking oil, the condenser coil is dirty, and the system is R-22 refrigerant which has been phased out. I brought all of this to the attention of the customer and made him a few options. HE elected to perform my top option. That option is detailed below: “Includes replacement of the capacitor, contactor, condenser fan motor, and a thorough rinsing of the condenser coil.” I rinsed the condenser off first and then replaced the contactor and capacitor. I then replaced the condenser fan motor. I gave the system power and gave it a call from the thermostat. Everything powered up properly. I checked refrigerant pressures and found them to be good for the amount of heat that is in the house. System is in working order at completion of appointment.