After performing the diagnostic, I found that the defrost control board has failed and is not sending the correct voltage through it. I also found that the starter has failed and is stuck closed. I presented the client with his options, and he chose to have it all replaced. We are ordering the control board and will return to install once it arrives. Trip 2 - Replaced the condenser control board, starter and added 2.5 lbs of R-410A refrigerant to the system. After performing the repairs everything is working at this time. I did find that the condenser fan motor is running hotter than it's supposed to and the secondary drain pan needs to be replaced. I presented my findings to the client.