My questions were answer, installers took care to cover any areas and cleaned up before leaving.
R- 410a Adjust Refrigerant level: Every pound after 1st RECOMMEND LEAK SEARCH BEFORE ADJUSTING REFRIGERANT CHARGE Purge gauges to ensure no non-condensables enter system Use digital scale to weigh in refrigerant Adjust according to units TP chart and super heat and sub cool
Arrived to home Found system down Breaker tripped Bad capacitors Contactor burnt Windings damaged
New 5 ton Trane XV18 split system to be installed, Includes new outdoor condenser with new base pad and disconnect box, New attic air handler with new hanging system, secondary drain pan, properly sized insulated plenums with manual dampers included for the supply side. Touch screen Wi Fi thermostat included.
Arrived to home Set thermostat to cool Checked condenser Found following Disconnect melted (non fuse original from 2001) Contactor burnt and pitted Capacitor swollen at 0/0 Compressor windings over heated needs inrush kit
Arrived to home Checked system Found insulation panels in evap cabinet came loose and were against coil Found evap coil 75% plugged w debris Start amps high - loud start noise Clean evap coil Flush drain Secure insulation to panels on coil Install easy start
I found system transformer tripped upon arrival. Verified low voltage wiring and reset. System is now communicating as it should. System is also low on r410a.
Arrived to home Checked system Settings good Temp split a little low Noticed discharge and SC fluctuating a little Will contact MFG on Monday
Provided maintenance on equipment and verified good operations. Compressor did have a shutter to its start. System is operating good at this time, suction pressure was a bit high for today’s indoor/outdoor temperatures but has good delta t (air temperature split) and good starting and operating amps. Noticed compressor has potentially experienced reverse rotation, would recommend a sure switch smart contactor with surge protection and short cycling protection to help prevent wear and tear on equipment.