Chris M.

Chris M. Job Checkin

Air balance


Charles B.

Charles B. Job Checkin

Arrived to home Checked system Found compressor cap bad Windings starting to wear out **wrong size cap installed (was 50 requires 45) Rewired fan to 3 wire set up and replaced cap with correct size Installed start kit Start amps at 40A Start kit and Dual Capacitor


Charles B.

Charles B. Job Checkin

I provided a check up on equipment and verified good operations.


Matthew B.

Matthew B. Job Checkin

Returned an installed the driver and verified operation and the unit is operating properly at this time


Camari D.

Camari D. Job Checkin

Includes Air Sealing & insulation in Buckeye


Charles B.

Charles B. Job Checkin

Checked thermostat for errror codes Multiple with 184.08 (hard lockout) Ran test cycle - shut off after 30 seconds or less Called Trane TS - went through drive test Checked ohms at compressor - .3/.3/.3 good Bad drive **if not under warranty cost to replace is $1610.10


Eric  A.

Eric A. Job Checkin

Trane HVAC Installation in Buckeye


Charles B.

Charles B. Job Checkin

Remove existing ODA cans on plenums Seal duct/plenum connection to ensure no more ODA is being brought into system and home Cleaning of all Clean Effects fee waived with this repair ______________________ Returned on 3/31/25 Removed all clean effects cells and pre filters Cleaned and blew cells Washed pre filters Dried off Removed all ODA cans After removing noticed filters had never been in place Interior of ducts extremely dirty Installed blank off and sealed


Charles B.

Charles B. Job Checkin

Repairs for master bedroom system Add refrigerant to system as the sub cool and pressures are low Change out the dual run capacitor which is currently at the lowest allowable measurement Changed capacitor - installed metal retaining bracket Upon arrival subcool was at 2.9 degrees Added 1.5# 410A - subcool now at 11 degrees System good at this time Can audibly hear 2 ton (master) valves in compressor-needs to be monitored-should possibly be a 3 or 3.5 ton system Would need to do a heat gain calculation to verify


Charles B.

Charles B. Job Checkin

Checked all systems Found all have 6” ODA ducts attached to return plenums - causing the clean effects to get dirty prematurely Game room unit - drain line was not attached - attached and cleared Cleared all drain lines for systems Cleaned all condenser coils for systems Systems operating mechanically and electrically within normal MFG specs at this time Discussed removal of ODA ducts to increase efficiency and prolong life of systems


Nixa G.

Nixa G. Job Checkin

Performed maintenance inspection in heating. No issues found at this time. Installed Reme Zero air purifier at this visit and homeowner renewed maintenance plan.


Nixa G.

Nixa G. Job Checkin

Performed inspection in heating. No issues found at this time. Homeowner explained master bedroom is the warmest room, and misses has seasonal allergies. I have attached the maintenance plans available to them and the whole home air purifier, Reme Zero.


Nixa G.

Nixa G. Job Checkin

Performed inspection in heating. No issues found with the equipment at this time. System is heating well at time of departure. There are known allergies and asthma within home. On today’s visit we were able to discuss some air quality improvement options to aid health. Proposal for options have been attached.


Charles B.

Charles B. Job Checkin

Checked both systems Master bed system = Had locking caps on line set Sediment trap installed upside down (inoperable) Pressures and sub cool low (low on refrigerant) Dual cap on compressor side at lowest allowable measurement Cleaned coil Unable to flush drain - need to replace existing stub out with either a union or safety switch Main home - 2 zone Master bed system = Had locking caps on line set System operating within MFG specs at this time Cleaned coil Unable to flush drain - need to replace existing stub out with either a union or safety switch Removed locks and installed brass self sealing caps


Charles B.

Charles B. Job Checkin

Checked system in cooling - changed filter in ERV - cleaned condenser and flushed drain - found system with low sub cool - added 7.4 oz of 410A sub cool now at 10.6 - tightened cores and caps - system good at this time