Matthew B.

Matthew B. Job Checkin

I found the wine cellar unit has a bad indoor blower motor. It’s a cartridge Mitsubishi mini split. The indoor unit does not have access and I recommended due to the age of the unit to replace it.


Matthew B.

Matthew B. Job Checkin

This system had high start amps and this will cut that amp draw in half. The other single stage unit has one already on it. Installed 2 surge protectors on xv condensers, I suggested putting them on the inside unit as well but homeowner didn’t think that was necessary so those are still unprotected but the drives are protected and that’s one of the biggest things we wanted to be safe.


Matthew B.

Matthew B. Job Checkin

Preformed winter tune up on all 4 units. All units are preforming within manufacturer specifications and found no major issues. I spoke to homeowner about getting on maintenance agreement but he had to leave so I left estimates for that and a couple other items that I think we should address. Both of the xv systems have no surge protection, I suggested them because specifically these units have expensive parts especially the drive that is back ordered months. We now put them on at install to protect our units because of this and suggest having them on unit to protect your investment. In addition one of the single stage units had high starting amps and no in rush device like the other unit. These can cut the amp draw in half and prolong the life of the unit. I changed all the filters except the casida as there was no new filter. I took a picture so homeowner can order the correct one. The other 3 had different filters in the closet that I was able to use. It’s up to the homeowner which


Matthew B.

Matthew B. Job Checkin

The outdoor stepper motor for the master bedroom has been chewed through and needs replaced


Chris M.

Chris M. Job Checkin

Test Erv, adjust air flow for master and guest AH, Find sound coming from guest side return.


Ryan T.

Ryan T. Job Checkin

Energy Audit in Paradise Valley


Matthew B.

Matthew B. Job Checkin

The condensation line was clogged, and I had no history of tuneups since the unit was installed. On the cool home membership tuneups the condensate line is flushed out. The air filters are very dirty and need replaced. Dirty air filters can contribute to a clogged condensate line. The condensation line was clogged, and I had no history of tuneups since the unit was installed. On the cool home membership tuneups the condensate line is flushed out. The air filters are very dirty and need replaced. Dirty air filters can contribute to a clogged condensate line. Clear Condensate Drain w/ Compressed gas -Inspect and clear PVC drain line -May require cutting existing line and installing coupler -Test drain line with water to ensure proper drainage


Alex W.

Alex W. Job Checkin

Found indoor air handler with no DC voltage to control boards, tested DC power supply by blower motor and found it was faulty. Replaced DC power supply and check system for proper operation. The personality error code was still present, so I power cycled all units and the error code was cleared. Outdoor fan motor was noisy and running at 2.89 AMPs when it’s rated for 2.80. Could not find any warranty information on the systems. Will follow up with Trane to see if the outdoor fan motor might be covered under parts warranty.


Matthew B.

Matthew B. Job Checkin

Both heads were calling for cooling. I checked the compressor and it’s electrically sound. The inverter board has LEDs and they are not lighting up. There’s no nomenclature for this system. I did a serial number look up with the Fujitsu and the unit so old Fujitsu does not recognize the serial. I left estimates for replacement


Matthew B.

Matthew B. Job Checkin

The kitchen unit was tripping on high head pressure. I bypassed the pressure switches to locate the liquid line or discharge restriction. The reversing valve was not fully switching and restricting the discharge line. I switched the valve back-and-forth eliminating the issue. The unit is operating under extremely high static pressures. The unit is operating properly for conditions at this time


Matthew B.

Matthew B. Job Checkin

The house has five package units and multiple issues with wall insulation and ductwork. Going to switch to have Alex come out and really assess the issues here.


Matthew B.

Matthew B. Job Checkin

I performed cooling preventative maintenance on all four systems. I did not check the garage unit. The casita unit has a bad dual capacitor and a burnt contactor. The other units had no issues.


Chris M.

Chris M. Job Checkin

Blower door testing in Paradise Valley


Elena C.

Elena C. Job Checkin

I found rodents had chewed the HP leads I removed the damaged leads and installed new leads and rerouted it. I wrapped the wires with foil tape to help protect


Chris M.

Chris M. Job Checkin

Mitsubishi mini split installation in Paradise Valley by Ideal Air Conditioning and Insulation