As I arrived, the homeowner showed me around the whole residence. It’s a three-story condenser is located on the roof air handler located on the third floor after looking over the system. We got the thermostat to turn back on, but the condenser was not acting right after going onto the roof, I found that the condenser was in heat mode, but the thermostat was set to cooling. Homeowner did say his thermostat went blank. when they were having the issues after going through the complete settings of the thermostat, I have reprogrammed the thermostat to the right settings for a heat pump. System is cooling properly. Drain line is draining properly in the house is starting to cool down. I do recommend a hard circuit on a condenser due to the amperage on every start up and a quiet down on the roof since it is on vibration pads, the capacitor is tested out perfectly and the Freon cap. I cannot get off, but I do have a good suction line and liquid line. Temp Coincides with the ambient temperatur