Customer concerned about unit not cooling properly. Checked thermostat calibration and filter location. Checked safety float switch and inspected drain line. Checked air handler coil and checked blower motor operation. Located bad uv lights in the air handler coil. Checked outside condenser unit and refrigerant pressure when running. Located low refrigerant charge in condenser unit. The condenser unit showed signs of oils from bottom of condenser unit. I have visible located leaking refrigerant from compressor manufacture fitting in condenser unit. The capacitor is weak and needs to be replaced with new capacitor. Needs the compressor replaced to repair leak in the system. Customer has approved for the compressor replacement and refrigerant added. Highly suggest to have uv lights replaced in air handler unit to prevent any biological growth in air handler coil. Bryant Model # 114cna036 Serial # 3318e27993 For compressor replacement needs recovery tank and machine to replace