Performed spring maintenance. Cleaned indoor and outdoor coil and cleared condensate trap. Tested system operation, system is in great working condition. Indoor blower is pulling 2 amps, outdoor fan motor is pulling 1.7 amps, compressor is pulling 6.3 amps. Had a 21 degree temperature difference between the return and the supply. Subcool was 10 and superheat was 12. Capacitor on outdoor unit is within manufacturer specifications at 44/45. Also tested condensate pump and it is in great working condition as well.