253 Timberlane Dr
Pisgah Forest, NC 28768
828-483-4040

Local Reviews
for candler, nc


Job Locations
for candler, nc

Jay E.

Jay E. Job Checkin

Outdoor fan is running with out the compressor. Checked Circuit board on heat pump to see if there was any LEDs that were flashing any codes. I couldn’t find any. I reset the power for three minutes turned it back on put my gauges on the unit left my Aunt probe on the incoming power temperature sensors on the indoor unit and started the system. I could hear the EXV opening heard the compressor start. With both heads calling for cooling and temperature set on the thermostat as low as possible forced outdoor unit into high. Amp draw is seven for the compressor and the fan. Delta T is 28 and refrigerant pressure is 120. I suspect that there might’ve been a power surge of some kind that caused the board not to start the compressor. But if this happens again, we’ll call tech-support and take a little deeper.


Cameron  S.

Cameron S. Job Checkin

Performed AC cooling tune ups on mini split systems checking all electrical, refrigerant balance, unit start u, operation, shutdown, cleaning of indoor and outdoor coils and treatment of drains. Everything looks and runs great!


Jay E.

Jay E. Job Checkin

Replaced broken heat strip and tested. Ultimate Cooling Tune-Up: cleaned coils, brushed and cleaned traps, added pan treatment tablets to pan. tested and checked all controls, wiring connections. tested temperatures, checked filters. checked refrigerant temperature and pressures, tested static duct pressure. tested blower operation, tested cooling operation to ensure working within manufacturer specifications. 1st floor system has media filter on furnace. You should not have filters in the walls. This double filtering and causes higher static pressure and bad airflow. Also this type of filter is a once a year filter. It’s in good shape. 2nd floor filters 14x14x1 and 18x18x1. You had 18x18 in mechanical closet. We will need to replace the 14x14x1. That filter didn’t look to bad.


Jay E.

Jay E. Job Checkin

Found short on heat strip DC relay. High voltage wire melted into the low-voltage wire. Heat strip should be under warranty as the systems only three years old. T030-0010 $152 to replace heatstrips. They should be in by Friday next week


Cameron  S.

Cameron S. Job Checkin

Found blower motor and blower wheel on furnace have failed. blower wheel has crashed into blower housing and has come apart. Parts have been found locally and can be replaced. Quoted 1366 + tax


Kevin S.

Kevin S. Job Checkin

Damper is flipped so it is spring closed and power open. If you look at the damper from the outdoor vent you can see it open when the vent hood comes on.


Kevin S.

Kevin S. Job Checkin

Delta T of 18 to 22 across all power heads. Treated outdoor coils with green cleaner. Rinsed kitchen power head with auto sprayer. Systems functioning normally.


Cameron  S.

Cameron S. Job Checkin

Replacement of 1/2" back flow preventer


Jay E.

Jay E. Job Checkin


Jay E.

Jay E. Job Checkin

Lake searched a package Nordine heat pump found the leak in a Schrader valve charge rate for Tony to manufacture specs system working perfectly on this mobile home in air-conditioning mode


Kevin S.

Kevin S. Job Checkin


Kevin S.

Kevin S. Job Checkin

Repaired bad capacitor on Nordyne packaged unit heat pump.


Jay E.

Jay E. Job Checkin

Air conditioning tuneup on 2 Mitsubishi heatpumps


Jay E.

Jay E. Job Checkin

Spring ultimate tuneup on a York to speed Honeywell zone system. Testing the air purifier Remi and global plasma solutions testing operation of a little giant condensate pump. Testing function of a Honeywell prestige 3.0 thermostat system

Spring ultimate tuneup on a York to speed Honeywell zone system. Testing the air purifier Remi and global plasma solutions testing operation of a little giant condensate pump. Testing function of a Honeywell prestige 3.0 thermostat system

Jay E.

Jay E. Job Checkin

Troubleshooting a rheem hot water commercial boiler