Preformed spring maintenance on system. Cleaned indoor and outdoor coil. Vacuumed out condensate trap. Tested system operation. System is in great working condition Compressor is pulling 5 amps, outdoor fan motor is pulling 1.4 amps. Indoor blower is pulling 1.1 amps. Temperature difference between return and supply is 23 degrees. Subcool was 8 and superheat was 11. Capacitor is within manufacturer specifications 35/35 and 5/5. Contactor is in great shape with no signs of charring.