Spring tune up Cleaned both indoor and outdoor coil, tested system operation. Incoming voltage is 245.7 compressor is pulling 10.2 amps, condenser fan motor is pulling 1.3 amps. Super heat is 6 and sub cooling is 14. Indoor blower was pulling 2 amps. System had a 19 degree temperature difference.