System had almost no refrigerant. Found leak on equalizer tube of txv. Repaired leak. Pull vac to 500 microns add charge to manufacture specs. Tested ac operation no other issues found Replaced service caps as the old cap O-rings were bad. Clean coil on outdoor unit.