Today I arrived on site and performed a winter time maintenance on your HVAC equipment. **Indoor Unit (Air Handler in Garage):** * Checked the 20x20x4 pleated filter (2-6"). Customer will provide their own filters. * Confirmed the indoor coil is clean and in fair condition. **Outdoor Unit (Heat Pump on Side of House):** * Verified the outdoor coil is clean and in fair condition. **Electrical Components:** * Tested and confirmed proper operation of: blower motor, heat strip kit, condenser fan motor, compressor, compressor run capacitor, fan run capacitor, contactor, and electrical wiring. **System Components:** * Inspected and confirmed good condition and proper operation of: blower wheel, primary drain pan, and secured electrical wires. **System Readings & Adjustments:** * Measured a return air temperature of 74.0°F and a supply air temperature of 104.3°F. * Cleared the condensate drain line, cleaned out the primary pan, and tested the safety switch. **Addition