08/05/2025- the control board is in stock at carrier, the one bag of 8 inch and 6 inch flex ductwork will be delivered to the shop tomorrow morning. 08/07/2025- I arrived on site and replaced the 8 inch and 6 inch ductwork lines that were pinched and restricting airflow with new flex ductwork. I was also able to get to the third duct that was giving the homeowner no airflow in her office and discovered that this duct wasn’t pinched, but loose and disconnected from the main duct line. I have resecured this loose duct back to the main duct line. All ductwork is now run without being pinched as well as connected properly. However I was unable to remove the old 6 inch duct line that I disconnected from the crawl space due to how pinched it was and how tight the crawl space is. I have informed the homeowner to not be alarmed if he sees this duct since it is not connected to the main duct line or a supply vent, it is only there because I was unable to remove it from the crawl space. I have