**Job Summary** Today, I arrived on site to perform summer maintenance on the HVAC equipment. **Overall Equipment Condition** - Equipment condition is good. **Indoor Unit** - Location: Closet - Type: Air Handler - Services: Whole home - Filtration: Antimicrobial filter checked and replaced today - Filter Size: 16x25x1 - Indoor Coil Condition: Good and clean **Outdoor Unit** - Location: Side of House - Type: Heat Pump - Outdoor Coil Condition: Good and clean; cleaned today **Electrical Components** - Tested and inspected the following components, all working properly: - Blower Motor - Condenser Fan Motor - Compressor - Blower Run Capacitor - Compressor Run Capacitor - Contactor - Defrost Control Board - Electrical Wiring - Noted that the Condenser Fan Motor Run Capacitor is not functioning properly. **Inspections** - Components in good condition: - Blower Wheel - Electrical Wires Secured - Primary Drain Pan - No components found in poor condition. **Temperat