Upon my arrival I checked into the concerns of water leaking from the ceiling in the break room. Performing my diagnostics I found that the drain line has become restricted causing the condensation to leak over into the emergency drain pan then was leaking past the not very well sealed drain port on the emergency drain pan. I spoke with Travis about my concerns and got approval to make corrective actions to the drainage system and seal the emergency drain pans port. I performed the approved repairs then stress tested the system with water verifying proper flow the treated it with drain pan solution. When we perform the evaluations we will be looking at each drain line to make quotes on adding in inline access ports to allow for better clearing of the drain line.