1503 U.S. 301
Tampa, FL 33619
813-580-8800

Local Reviews
for treasure island, fl


Job Locations
for treasure island, fl

Brennan  G.

Brennan G. Job Checkin

14.3 SEER2 GOODMAN / 1.5TON STRAIGHT COOL 5kw Electric heaters 10 Year parts warranty 1 Year Labor warranty 1st year Maintenance Job Includes: Required permits and inspections Required electrical upgrades (breakers only) Crane Rx11 Line-set Flush Chemical drain flush Float switches Supply plenum Duct sanitation Hurricane Straps Leave existing thermostat

14.3 SEER2 GOODMAN / 1.5TON STRAIGHT COOL 
5kw Electric heaters 
10 Year parts warranty 
1 Year Labor warranty 
1st year Maintenance 
Job Includes:
Required permits and inspections 
Required electrical upgrades (breakers only)
Crane
Rx11 Line-set Flush 
Chemical drain flush 
Float switches
Supply plenum 
Duct sanitation 
Hurricane Straps 
Leave existing thermostat

Brennan  G.

Brennan G. Job Checkin

Brennan G Emailed Larry a revised quote. Larry agreed to have us do the system change out Jeanette to email new sales slip, collect $2000 deposit and schedule job with Larry.

Brennan G
Emailed Larry a revised quote. Larry agreed to have us do the system change out
Jeanette to email new sales slip, collect $2000 deposit and schedule job with Larry.

Brennan  G.

Brennan G. Job Checkin

Brennan G Todays visit was to finalize the system replacement Larry chose the 1.5ton 15SEER Goodman Is going to pay a $2000 deposit (service titan not working properly at time of visit) And the remainder (6198.14) will be funded through synchrony 25months 0% interest. Sales slip singed , job scheduled for next Friday 05/05/22

Brennan G
Todays visit was to finalize the system replacement 
Larry chose the 1.5ton 15SEER Goodman 
Is going to pay a $2000 deposit (service titan not working properly at time of visit)
And the remainder (6198.14) will be funded through synchrony 25months 0% interest.
Sales slip singed , job scheduled for next Friday 05/05/22

Brennan  G.

Brennan G. Job Checkin

Brennan G Completed check up 2007 Comfort maker 1.5ton Straight Cool System is cooling at this time However discovered multiple areas of concern throughout todays visit. The indoor blower motor is covered in oil, indicating it has overheated The evap coil is rusted. The compressor fan dual capacitor is weak , over the 3% tolerance rating. The compressor contactor is pitted. The compressor is reading caution on the megohmeter reading. Gave repair and replacement quotes. Will follow up with client unable to discuss estimates he is working from home at the time of service.

Brennan G
Completed check up
2007 Comfort maker 1.5ton Straight Cool
System is cooling at this time 
However discovered multiple areas of concern throughout todays visit.
The indoor blower motor is covered in oil, indicating it has overheated 
The evap coil is rusted.
The compressor fan dual capacitor is weak , over the 3% tolerance rating.
The compressor contactor is pitted. 
The compressor is reading caution on the megohmeter reading.
Gave repair and replacement quotes.
Will follow up with client unable to discuss estimates he is working from home at the time of service.

Tony L.

Tony L. Job Checkin

Repair Option, completed Found blower overheated and clogged with insulation from air handler,cleared blower and checked capacitor and amp draw,blower checked good. Customer will see if blower continues to work and will either replace system or have maintenance done.

Repair Option, completed 
Found blower overheated and clogged with insulation from air handler,cleared blower and checked capacitor and amp draw,blower checked good.
Customer will see if blower continues to work and will either replace system or have maintenance done.

Tony L.

Tony L. Job Checkin

1 Time Maintenance

1 Time Maintenance