Fixed the drainage pipe
estimates for new duct work
Replace faulty capacitor 45/5 and maintenance complete. Unit is running normal.
Replaced failed ss2 float switch. Made sure that system is running and cooling properly. System is running and cooling properly. No further issues are found
Upon inspection in attic find no source of water leaking from unit onto range vent. Range vent is clear from any piping to air handler
Needs new ss3 or nstalled system up and running
Today we visited because the AC wasn’t working. Scott cleaned the drain and that didn’t fix it. The issue was a bit of leftover water in the float switch. After resetting the switch the unit came on and performed as it should.
Repair Option cutout for return grill needs to be cut out bigger
Wiring issues have been repaired system up and running
Today we visited to determine why the AC isn’t working. We found the unit low on refrigerant and uncovered a leak in the evaporator coil. The coil needs to be ordered, but we can charge the unit with refrigerant while we wait for the parts.
Today we visited to follow up from a recent visit with our technician. The air conditioning system has had multiple problems, primarily dealing with moisture since installation. We learned the system is not installed to code, has incorrect static pressure, and does not have enough pitch on the drain system. James completed an evaluation and drawing of the home to put together a report detailing the issues observed, and the necessary remedy.
800 CFM antimicrobial replacement/redesign
800 CFM antimicrobial replacement/redesign
Today James visited to reevaluate the ductwork installation. Bob and bath, remodeled their home and changes the floor plan. There will be three additional vents added, as well as a platform and manual dampers.