I performed cooling preventative maintenance in the system. The disconnect was melted together and the contactor was burnt from high starting amps. The indoor TXV was never adjusted to the proper super and sub. The system displayed a low charge. I replaced the disconnect and contactor. I added a start assist and adjusted the indoor TXV to factory specifications. I charge the unit with 2.2 poundsThe unit is operating properly