Called out today due to no cooling. Upon arrival system was running but shut off after two minutes. Checked all electronics and motor components to ensure equipment is operating properly within manufacture specifications. Filter is impacted, client will replace. Drain line is heavily clogged with algae build up. Checked refrigerant pressures. Client approved drain solve treatment. Chemically treated drain line. Flushed four gallons of water while vacuuming. Showed client how to flush her drain line in between tune ups. Removed the fan from the condenser and cleaned the coil from the inside out. Equipment is operating properly at this time. Thank you for always choosing Total