OFFICE please note all buildings on this property require a 30 foot ladder to access the condensers on rooftops. No cool Upon arrival, found system set in cooling with the air handler running but no condenser. After opening condensing unit found mushroomed capacitor. Capacitor readings were under .5 µF. Replaced 35+5 µF capacitor. Reset compressor core sense. Checked refrigerant, pressures, and temperatures. The system is running and cooling again.