Job Checkin

03/28/24 - No Cool - updated equipment on IMAST Dispatch see attached notes Upon arrival the T-sat was in the off position. System was tripped on float switch & I found dirty evaporator coils. (Dirt falls into the evaporator drain pan & restricts water flow. The drain line is installed to where it runs under the CU with no access to flush & vacuum the drain line & no p-trap is installed, we did not do the install. Verified pressures & temperatures & they were within manufacturing specs. Recommended signing up or our Air Care monthly membership which includes 2x system check’s per year & 20% off repairs & cleanings. Also recommend a evaporator clean n place be performed with a chemical drain line treatment. I recommend that a small piping repair be performed to cut back the drain line for access to flush & vacuum & adding a P-trap. A UV KIT was recommended to curb biological growth development across the evaporator coils & avoid costly cleanings & breakdowns. Recommend having blown