Checked all major components: Freon levels compressor , fan motor , capacitor, rinsed condenser coil, flushed drain line , checked filters . Based on readings capacitor is reading lower than it’s rated and contractor points are burned and are making compressor to work hard . Unit is 14 years old . Recommend customer to see options for a new unit. Customer wanted to replace capacitor and contractor for now.