Preformed tune up on both systems Could not get emergency heat to work on mother in law suite. Found ecobee thermostat was wrong application for this system. Replaced with Honeywell wifi thermostat and tested system operation. System now works as it should. mother-in-law suite blower is pulling .54 amps Has a 24 degree temperature difference from heat pump. Outdoor fan motor is pulling .43 amps, compressor is pulling 5.6 amps. Heat strip is pulling 18.2 amps and has a temperature difference of 15. Main system blower is pulling .8 amps and has a 30 degree temperature difference on the heat pump. Compressor is pulling 4.5 amps and outdoor fan motor is pulling .7 amps. Electric heat is pulling 41 amps and has a 25 degree temperature difference. Both systems are in great shape and everything is working properly.