Performed spring maintenance Outdoor compressor is pulling 7 amps Outdoor fan is pulling 1.3 amps Indoor blower is pulling 1 amp System has a 22 degree temperature difference. Superheat is 10 and subcool is 11 Cleaned indoor and outdoor coils Cleared condensate trap. Replaced filter Tested zone dampers, all dampers are working correctly. System is in perfect working condition.