Customer said that the unit was not heating. Found the fuse to be popped. Replaced fuse and watched unit run. Fuse popped after ~40 minutes of running. Checked wiring and found a small rub through of insulation on the high pressure switch wires. Taped up switch and let unit run for 40 minutes and it ran with no issue. Thank you for your business.