Sam J - arrive to perform a summer service on a blue club member. Customer greeted me in the garage, and we discussed the performance of the system. Customer has no issues to report at this time. Disconnected power to the condensing unit, then clean condenser and check components. I then moved into the attic and checked the ductwork. Also recorded amperage of blower motor and capacitor. Powered up condensing unit and recorded amperage of compressor and fan motor. I then recorded superheat and sub cooling values after allowing coil to dry after several minutes of runtime. Set thermostat back to preferred setpoint and spoke with customer about today’s visit. System is operating properly at this time. [Furnace] Blower - 6.31 (9.5A) Run capacitor - 14.3mfd (15.0mfd) [Condenser] Run capacitor - 43.5/9.7mfd (45/10mfd) Start capacitor - N/A Compressor - 9.59RLA (17.9A) Fan - 0.96RLA (1.20A) Subcool - 5.6 degrees (N/A)