15JUL2023 Jason Brown Arrived for new customer no cool. Spoke with Carlos about the systems performance. It was out went I got home. I checked the drains and looked for error codes but everything looked good. My AC guy is at the lake today and I need to get this running. Inspected furnace coil and thermostat. Thermostat in on position set to 69 reading 74 opened blower compartment and inspected wheel and motor. Removed piece of ductboard from wheel causing vibrations. Inspected drains found some water In float switch cup. Tested condensate pump. Pump operating normally. Buttoned up equipment and system fired up. Inspected outdoor condenser coils, compressor, fan, capacitor and contactor. Found all operating within manufacture specs. Measured delta T found 16 degree temp split. Recommended more insulation on lineset to prevent dripping in closet. System is working properly at this time.