03AUG2023 Jason Brown Arrived for silver club summer tune up service. Spoke with staff about the systems performance. They’re struggling in the heat but that’s normal with the 4th system down. Verify thermostat operation, replace batteries in workshop. Replace 6 25x25x2 1 16x25x1 Wash all condenser coils, check caps and amps. Verify pressures and motors. All systems are running to the best of their abilities at this time. Workshop thermostat has loose connection. Recommend replacement Rtu #1 blower 6a filters Changed caps 7.4/7.5& 7.5/7.5 washed condenser coils. Coils 50% Pressures good Rtu#2 blower 5.7a filters changed 7.5/7.5 7.1/7.5 coils damaged Pressures good. IDU#1 coil clean blower clean cap 19/20 amps 5.3 system operation normal AC-fan .7a comp 15/19a cap 44/45 5/5 pressures good.