Came out to call for a system not cooling properly and owner of business also wanted to know the details of the 4 Ton package unit that is not operational. I checked south east 7.5 ton unit not cooling well and found one of the compressors not pumping. Checked high pressure switch reset and the compressor came on. Condenser coils are badly damaged from hail, and is something we’ve noted on the account for awhile. Systems are due for maintenance and need cleaning. Checked 4 ton package unit out and found it not having proper voltage on 3 legs of power. Only getting 200 volts and need 240. Unit has a known small leak in the condenser coil that is no longer made via manufacturer. Discussed with customer about repair options and replacement. Customer stated the owner of the building wants to try to have the unit fixed before they talk about replacement. Customer will have to have an electrician out to fix power issue before we can address the system. I will put this call on hold till custo