Once sewage pit was completely drained we cleaned out debris in pit and flushed out both pumps. One pump had several wipes and chunks of metal lodged in the blades not allowing it to properly run. After performing inspection on pumps and diagnosing control panel for the pumps we found the following - one pump was not working properly (recommend replacement) - control panel is wired incorrectly as well as missing several control boards, and has burned fuses that all need to be addressed. In order to restore proper function to system we will need to replace one pump, order Several parts for control panel and wire in pumps and floats correctly to panel. For control panel we called manufacture and they helped us diagnose issues and are following their recommendations. Once these new parts are installed we can then run further test to make sure everything is in proper working order.