Customer has a leak in his 3/4” copper hot water line that goes from his water heat over to kitchen sink that we recommended re-routing. Performed re route of customers hot 3/4” copper water line from behind water heater over to behind kitchen sink manifold. Pressurized customers system and Listened with leak detection equipment to exposed manifold and didn’t hear any water running, we also checked the meter to see if meter was moving. At first meter was not moving which tells us there were no further leaks. At the end of cleaning up we checked meter again and meter was spinning very slowly, walked around the property and noticed customers T&P relive valve was dripping into plater bed on side of the house and customers back hose bib was dripping as well which could lead to the reason for meter spinning. Customers gate valve to shut off the water to the house as well as the gate valve for sprinklers and water heater where not working so we where not able to isolate the different s