Upon arrival thermostat was blank and indoor and outdoor unit wasn’t working. Checked breakers, jumped R and G at thermostat, checked power coming in, checked transformer. Disconnected primary float switch, iFlow, and Condensate pump. After troubleshooting found the pump to have failed. Most likely took a surge during the storm. We installed this pump in the Last few weeks. Temporarily installed a 120v pump using the bathroom outlet. Office we will need to come back and install a 230v pump and wire directly into the unit. Customer asked about warranty. Office please verify with storm. Used green sky application ID to add the full price of a new pump and service fee. Refrigerant levels and delta temp are good.