Arrived onsite and spoke to homeowner and she mentioned the system came on once. I turned thermostat on and found that the indoor unit was running and outdoor unit was running as well but without the compressor. I checked the capacitor and it was working okay. Checked thermal on compressor and it was not in thermal lockout. Plugged disconnect back in and caught the unit pulling 269 amps and system is LRA 77 amps. Recommended a maintenance contract and recommended either replacing the unit or replacing the compressor. Compressor is under warranty till next year 5/17/26.