403 Headquarters Dr. Unit 5
Millersville, MD 21108
(443) 396-3797

Job Locations
for columbia, md


Map of Columbia MD
Ian  M.

Ian M.


Job Checkin

For this job, I came out to take a look at 110 amp breaker in the main panel supplying a disconnect feeding an electric furnace. Within the disconnect is a 50 amp breaker for the heat pump and a 60 amp for the auxiliary heat, feeding the unit from the disconnect. I checked all points of service from electrical standpoint at each point of disconnect. I did find loose connections on the load side in the disconnect at the breakers where I got multiple full rotations tightening the screw on the breaker. During our diagnostic, we had the customer turning the auxiliary heat on in addition to heat pump running and performed a load test with no abnormal findings. I pulled the breaker out of the panel as well and everything looked fine. This is the first season during the brutal cold with there less than 5 year old unit having an issue. I believe it was just working as hard as it could to pump and provide heat during that time as the customer stated it would typically happen at night during the

For this job, I came out to take a look at 110 amp breaker in the main panel supplying a disconnect feeding an electric furnace. Within the disconnect is a 50 amp breaker for the heat pump and a 60 amp for the auxiliary heat, feeding the unit from the disconnect. I checked all points of service from electrical standpoint at each point of disconnect. I did find loose connections on the load side in the disconnect at the breakers where I got multiple full rotations tightening the screw on the breaker. During our diagnostic, we had the customer turning the auxiliary heat on in addition to heat pump running and performed a load test with no abnormal findings. I pulled the breaker out of the panel as well and everything looked fine. This is the first season during the brutal cold with there less than 5 year old unit having an issue. I believe it was just working as hard as it could to pump and provide heat during that time as the customer stated it would typically happen at night during the For this job, I came out to take a look at 110 amp breaker in the main panel supplying a disconnect feeding an electric furnace. Within the disconnect is a 50 amp breaker for the heat pump and a 60 amp for the auxiliary heat, feeding the unit from the disconnect. I checked all points of service from electrical standpoint at each point of disconnect. I did find loose connections on the load side in the disconnect at the breakers where I got multiple full rotations tightening the screw on the breaker. During our diagnostic, we had the customer turning the auxiliary heat on in addition to heat pump running and performed a load test with no abnormal findings. I pulled the breaker out of the panel as well and everything looked fine. This is the first season during the brutal cold with there less than 5 year old unit having an issue. I believe it was just working as hard as it could to pump and provide heat during that time as the customer stated it would typically happen at night during the