David Solomon was attentive, knowledgeable, and thorough. Besides all that he was very friendly and communicated very well. Thanks David
Was a quick check up on our fire extinguishers, quickly replaced the ones that were outdated and was a good conversationalist.
Semmiannual Kitchen Inspection Scheduled with Laura 908-918-0600
Scheduled with Donna (site) #908-273-1300 The following discrepancies were found during your Annual Fire Inspection that needs to be corrected for Compliance: (6) 10# ABC extinguishers are due for 6 year maintenance. (1) 5# ABC extinguisher is due for 6 year maintenance. (1) 2.5# ABC extinguisher is due for replacement.
COD $383.31 Semmiannual Kitchen Inspection (2 - 2.5 Gal RG) Scheduled with Willy 908-277-0990
CUSTOMER IS MAILING IN A DEPOSIT CHECK OF $603.00 Scheduled with Nick 908-273-9600 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: Appliances configuration in cooling line has changed. Nozzles protecting griddle, char broil, fryers, 48” range and salamander broiler need to be adjusted to put in correct position. Incorrect protection of 36” range due to back shelf, must replace NL-1HP with NL-2LP nozzle and relocate 6” above front edge and aimed 6” off back wall.